Technical Summary
| Product type designation | KTP400 Basic mono PN |
|---|---|
| Display design | STN |
| Screen diagonal | 3.8 in |
| Number of colors | 4; Grayscales |
| Horizontal image resolution | 320 pixel |
| Vertical image resolution | 240 pixel |
| Number of function keys | 4 |
| Touch screen | Yes; Analog-resistive |
| Type of supply voltage | DC |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption (rated value) | 0.1 A |
| Active power input, typ. | 3 W |
| Number of industrial Ethernet interfaces | 1 |
| PROFINET | Yes |
| EtherNet/IP | Yes |
| TCP/IP | Yes |
| MODBUS | Yes; Modicon (MODBUS TCP/IP) |
| IP (at the front) | IP65 |
| IP (rear) | IP20 |
| Product lifecycle | Product cancellation |
Applications
Use as an HMI panel for key/touch operation and display of machine or process information.
Use for connection through 1 industrial Ethernet interface with PROFINET and related Ethernet protocols.
Key Features
KTP400 Basic mono PN
Key/touch operation with 4 function keys and an analog-resistive touch screen
4" STN display with 4 gray levels, 320 pixel horizontal image resolution, and 240 pixel vertical image resolution
1 industrial Ethernet interface with PROFINET, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP, LLDP, and MODBUS; Modicon (MODBUS TCP/IP)
24 V DC supply, vertical mounting position, and mounting possible in portrait format and landscape format
Product cancellation
Frequently Asked Questions
What is the exact Siemens model number of this HMI panel?
The exact model number is 6AV6647-0AA11-3AX0.
What display and operation type does the KTP400 Basic mono PN have?
It has a 4" STN display with 4 gray levels and key/touch operation with an analog-resistive touch screen.
What is the supply voltage for this Siemens HMI panel?
The supply is DC, rated value 24 V, with a permissible range of 19.2 V to 28.8 V.
Which communication interfaces and protocols are available?
It has 1 industrial Ethernet interface and supports PROFINET, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP, LLDP, and MODBUS; Modicon (MODBUS TCP/IP).
What lifecycle status is given for this part?
Product cancellation.