Technical Summary
| Product type designation | DQ 16x24VDC/0.5A HF |
|---|---|
| Product function | I&M data: Yes; I&M0 to I&M3 |
| Operating mode | DQ |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range, lower limit (DC) | 19.2 V |
| Supply voltage, permissible range, upper limit (DC) | 28.8 V |
| Digital outputs, number | 16 |
| Digital outputs, type | Transistor |
| Digital outputs, current-sourcing | Yes |
| Switching capacity, output current for signal "1" rated value | 0.5 A |
| Switching capacity, current per group, max. | 4 A |
| Switching capacity, total current per module, max. | 8 A |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
Applications
Provides 16 digital outputs for controlling output signals.
Supports single-channel diagnostics and substitute values for output monitoring and maintenance handling.
Key Features
DQ 16x24VDC/0.5A HF TX rail based on 6ES7522-1BH01-0AB0.
Designed with conformal coating.
Digital output module with 16 channels in groups of 8.
Current per group: 4 A.
Single-channel diagnostics are supported.
Substitute value: Yes.
Frequently Asked Questions
What is Siemens 6AG2522-1BH01-4AB0?
It is a SIPLUS S7-1500 DQ 16x24VDC/0.5A HF digital output module.
How many digital outputs does 6AG2522-1BH01-4AB0 have?
It has 16 digital outputs in groups of 8.
What supply voltage does this module use?
Rated supply voltage is 24 V DC, with a permissible range from 19.2 V DC to 28.8 V DC.
Does 6AG2522-1BH01-4AB0 support diagnostics?
Yes, it supports diagnostics function, single-channel diagnostics, alarm and maintenance interrupt functions, and substitute values can be connected.
What lifecycle status is supplied for this Siemens part?
Active Product.