| Product type designation | Active backplane ST 1+12 slot |
|---|---|
| Based on | 6ES7590-0BL00-0AA0 |
| Product function I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Prioritized startup | Yes |
| Power consumption from the backplane bus | 2 W |
| Power loss, typ. | 2 W |
| Number of slots | 13 |
| Ambient temperature during operation, horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| Ambient temperature during operation, horizontal installation, max. | 70 °C; = Tmax |
| Ambient temperature during operation, vertical installation, min. | -40 °C; = Tmin |
| Ambient temperature during operation, vertical installation, max. | 40 °C; = Tmax |
| Product lifecycle | Active Product |
Applications
Provides a 12-slot active backplane bus for inserting S7-1500 I/O modules for hot swapping.
Used in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
Key Features
Active backplane bus with 12 slots for inserting S7-1500 I/O modules for hot swapping.
Supplied with conformal coating for the SIPLUS variant.
-40…+70 °C.
For use in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
Active Product.
Frequently Asked Questions
What is Siemens 6AG1590-0BL00-7AA0?
It is a SIPLUS S7-1500 active backplane bus with 12 slots.
How many slots does 6AG1590-0BL00-7AA0 have?
It has 13 slots in total, with 12 single-width slots maximum.
What is the power consumption of 6AG1590-0BL00-7AA0?
Power consumption from the backplane bus is 2 W.
What are the operating temperature limits for 6AG1590-0BL00-7AA0?
Horizontal installation: -40 °C to 70 °C. Vertical installation: -40 °C to 40 °C.
Which system use is specified for 6AG1590-0BL00-7AA0?
It is for use in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.