Technical Summary
| Product type designation | AI 4xI 2-/4-wire ST |
|---|---|
| Number of analog inputs | 4; Differential inputs |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 37 mA; without sensor supply |
| Power loss, typ. | 0.85 W; Without encoder supply voltage |
| Address space per module, max. | 8 byte; + 1 byte for QI information |
| 2-wire connection | BU type A0, A1 |
| 4-wire connection | BU type A0, A1 |
Applications
Use for 4 differential analog inputs with current measurement as 2-wire transducer and 4-wire transducer.
Use for integration into ET 200SP systems with BU type A0 or A1 connection variants.
Key Features
AI 4xI 2-/4-wire ST analog input module for the ET 200SP system.
Number of analog inputs: 4; Differential inputs.
2-wire connection: BU type A0, A1. 4-wire connection: BU type A0, A1.
Rated value (DC): 24 V; permissible range: 19.2 V to 28.8 V.
Conformal coating, module diagnostics, diagnostics function, and monitoring of the supply voltage.
Product lifecycle: Announcement of product phase-out.
Frequently Asked Questions
What is the exact Siemens order number and module type for 6AG2134-6GD01-1BA1?
It is a SIPLUS ET 200SP AI 4xI 2-/4-wire ST analog input module.
How many analog inputs does 6AG2134-6GD01-1BA1 have?
It has 4 differential analog inputs.
What supply voltage does 6AG2134-6GD01-1BA1 require?
Rated value (DC): 24 V; permissible range: 19.2 V to 28.8 V.
Which BaseUnits can be used with 6AG2134-6GD01-1BA1?
BU type A0 and A1 are supported for both 2-wire and 4-wire connection variants.
What lifecycle status is listed for 6AG2134-6GD01-1BA1?
Product lifecycle: Announcement of product phase-out.